Siemens LMV36.520A1 Basic Documentation page 195

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

/reset
or
/reset
ESC
To the next parameter
/reset
To the next parameter
 For operating modes 1...4, 7...10, 12...16 and 19...22, refer to chapter Setting curvepoints P0, P1
and P9 for modulating mode («G mod», «Gp1 mod», «Gp2 mod» and «Lo mod»)
 For operating modes 5, 6, 11, 17 and 18, refer to chapter Setting the curvepoints for multistage mode
(«Lo 2-stage» and «Lo 3-stage»)
To the next parameter
Building Technologies Division
Infrastructure & Citiies Sector
P
V
h min s
P
V
h min s
P
V
h min s
P
V
h min s
P
V
h
s min %
P
V
h
s min %
Basic documentation LMV36...
28 Parameter level
Press
to go to editing mode.
/reset
%
Press
or
setting.
Example: 3 for gas modulating with pilot valve
%
(Gp2 mod)
Press
to save the selected setting.
/reset
%
ESC
Press
to return to the parameter level.
%
Press
to change to parameter 542: to
/reset
activate the VSD / PWM fan.
You can choose:
0 = VSD / PWM fan OFF
1 = VSD / PWM fan ON
Press
to change to parameter 641: to
control speed standardization of the VSD.
You can choose:
0 = speed standardization of VSD OFF
1 = speed standardization of VSD ON
After setting speed standardization to 1,
standardization of the VSD commences. If
successful, the parameter is reset to 0.
Negative values indicate errors (refer to chapter
Automatic speed standardization).
to select the required
Back to the previous
parameter
195/248
CC1P7544en
25.09.2013