Error History; Error Classes - Siemens LMV36.520A1 Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

152/248
Building Technologies Division
Infrastructure & Citiies Sector

20 Error history

The LMV36... system provides an error history in which the last 25 errors are stored.
The first entry represents the current error state and can also be error-free, refer to Error
code list.
Error
Diagnostic
code
code
200 OFF
#

20.1 Error classes

The errors are subdivided into error classes, depending on the severity of the switch-off
response. The current error shows all classes. Only the errors of the most important
classes are included in the history.
Error class
Priority
0
Highest
1
2
3
4
5
6
Lowest
Basic documentation LMV36...
20 Error history
Meaning for the LMV36... system
System error-free
Meaning
Lockout
Safety shutdown with software reset
Undervoltage
Safety shutdown: Safety phase
Safety shutdown: Start prevention
Safety shutdown: Shutdown
Message without shutdown response
History
CC1P7544en
25.09.2013

Hide quick links: