With select: Error code 210 diagnostic code 0
The VSD can be used with any of the operating modes (refer to chapter VSD).
No.
Parameter
Activation of VSD / PWM fan
542
0 = inactive
1 = active
Note
For configuration of the analog output when the VSD is activated, refer to
chapter Load output X74 pin 3!

9.1 Deleting curves

To delete curves, the operating mode must be set to undefined «--». In that case, only
the fuel curves are deleted, the direction of rotation or the reference position of the
actuators is not changed.
Basic documentation LMV36...
9 Selection of operating mode
Description
Heavy oil direct ignition without circulation control, electronic 2-stage
ratio control. Optional with VSD with speed feedback signal
Heavy oil direct ignition without circulation control, electronic 3-stage
ratio control. Optional with VSD with speed feedback signal
CC1P7544en
25.09.2013