Siemens LMV36.520A1 Basic Documentation page 225

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
LMV36...
Repetition limit value loss of flame
380
1 = no repetition
2 = 1 repetition
Fuel 1 oil: Point in time oil is ignited
381
0 = short preignition (Ph38)
1 = long preignition (with fan) (Ph22)
384
Fuel 1 oil: Postpurge time 3 (abortion if load controller ON)
385
Fuel 1 oil: gas pressure switch-min with «Lo Gp»
0 = inactive
1 = active
400
Ratio curves
401
Ratio control curves fuel actuator (curve setting only)
402
Ratio control curves air actuator (curve setting only)
403
Ratio control curves VSD (curve setting only)
404
Fuel 1: Ratio control curves fuel actuator (curve setting only)
405
Fuel 1: Ratio control curves air actuator (curve setting only)
406
Fuel 1: Ratio control curves VSD (curve setting only)
500
Ratio control
501
No-flame positions fuel actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
502
No-flame positions air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
503
No-flame speeds VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
Building Technologies Division
Infrastructure & Citiies Sector
Number of
Type
Edit
elements
1
Std_u8
Edit
1
Selection
Edit
1
Time
Edit
1
Selection
Edit
13
Std_s16
Edit
13
Std_s16
Edit
13
Std_s16
Edit
13
Std_s16
Edit
13
Std_s16
Edit
13
Std_s16
Edit
3
Std_s16
Edit
3
Std_s16
Edit
3
Std_s16
Edit
Basic documentation LMV36...
29 Parameter list LMV36...
Value range
Resolution
Min
Max
1
2
1
0
1
1
1 s
108 min
0.2 s
0
1
1
0 °
90 °
0.1 °
0 °
90 °
0.1 °
15 %
100%
0.1%
90°
0.1°
90°
0.1°
15 %
100 %
0.1 %
0 °
90 °
0.1 °
0 °
90 °
0.1 °
0%
100%
0.1%
Default
Password level
setting
1
OEM
0
SO
1 s
SO
0
SO
0 °; 0 °; 15 °; undefined
SO
0 °; 90 °; 45 °; undefined SO
0%;
100%;
50%;
SO
undefined
0°, 0°, 15°, undefined
SO
0°, 90°, 45°, undefined
SO
0 %, 100 %, 50 %,
SO
undefined
Index
Value
SO
0
1
2
15°
Index
Value
SO
0
1
90°
2
45°
Index
Value
SO
0
0%
1
100%
2
50%
225/248
CC1P7544en
25.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agm60.4a9

Table of Contents