Referencing - Siemens LMV36.520A1 Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Building Technologies Division
Infrastructure & Citiies Sector

12.3 Referencing

An incremental transducer is used for position feedback. This means that referencing of
the actuators must be performed after power-ON. In addition, at the end of each
shutdown in phase 10, the actuators are referenced to ensure that individual stepping
errors, which could lead to shutdown, do not accumulate. If a position error occurs, the
system switches to the safety phase (phase 01), enabling the actuators with detected
position errors to be referenced. During the following phase 10, the only actuators
referenced are those that were not referenced before in the safety phase (phase 01).
The position of the reference point can be selected depending on the type of burner,
either the Closed position (<0°) or the Open position (>90°).
When using actuators SQM33.6 or SQM33.7, the actuator type (parameter 613) must
be set (refer to chapter Actuator type / running time).
Note!
If a SQM33.7 is used, the modulating operating ramp (parameter 544) may need to be
increased (refer to chapter Running speed / maximum curve slope).
Listed below settings for air apply to both fuels:
In single-fuel operation or in dual-fuel operation, the parameters 601...606 and 611
are assigned to fuel 0
In dual-fuel operation, the parameters 608...610 and 612 are assigned to fuel 1
Basic documentation LMV36...
12 Actuators X53 / X54
121/248
CC1P7544en
25.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agm60.4a9

Table of Contents