Technical Data; Lmv36; Terminal Loading Inputs - Siemens LMV36.520A1 Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

28/248
Building Technologies Division
Infrastructure & Citiies Sector
4

Technical data

4.1 LMV36... basic unit
Mains voltage
Mains frequency
Power consumption
Safety class
Degree of protection

4.1.1 Terminal loading Inputs

Perm. mains primary fuse
(externally)
Unit fuse F1 (internally)
Mains supply: Input current depending on the operating state of the unit
Undervoltage
Safety shutdown from operating
position at mains voltage
Restart on rise in mains voltage
Status inputs: Status inputs (with the exception of the safety loop) of the contact
feedback network (CFN) are used for system supervision and require mains-related
input voltage
Input safety loop
Input currents and input voltages
- UeMax
- UeMin
- IeMax
- IeMin
Contact material recommendation
for external signal sources (LP,
Pmin, Pmax, etc.)
Transition / settling behavior /
bounce
- Perm. bounce time of contacts
when switching on / off
UN
Voltage detection
- On
- Off
Basic documentation LMV36...
4 Technical data
AC 120 V -15 % / +10 %
50 / 60 Hz ±6 %
<30 W (typically)
I, with parts according to II and III to
DIN EN 60730-1
IP00
Note
The burner or boiler manufacturer must
ensure degree of protection IP40 for the
LMV36... as per DIN EN 60529 through
adequate installation
Max. 16 AT
6.3 AT (DIN EN 60127 2 / 5)
Approx. AC 93 V
Approx. AC 95 V
Refer to Terminal loading outputs
UN +10 %
UN -15 %
1.5 mA peak
0.7 mA peak
Gold-plated silver contacts
Max. 50 ms
(after the bounce time, contact must stay
closed or open)
AC 120 V
AC 90...132 V
<AC 40 V
CC1P7544en
25.09.2013