Siemens LMV36.520A1 Basic Documentation page 227

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
LMV36...
Index 1 = air
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
606
Tolerance limit of position monitoring [0.1°]
Index 0 = fuel
Index 1 = air
Greatest position error where a fault is securely detected
 error detection band: (P606-0.6°) to P606
608
Fuel 1: Selection of reference point
0 = closed (<0°)
1 = open (>90°)
609
Fuel 1: Actuator's direction of rotation
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
610
Fuel 1: Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
 Error detection band: (parameter 606 -0.6°) up to parameter 606
611
Type of reference
Index 0 = fuel
Index 1 = air
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1...)
3 = both
612
Fuel 1: Type of reference for fuel actuator
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1...)
3 = both
613
Type of actuator
Index 0 = fuel
Index 1 = air
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
Building Technologies Division
Infrastructure & Citiies Sector
Number of
Type
Edit
elements
2
Std_u8
Edit
1
Std_u8
Edit
1
Std_u8
Edit
1
Std_u8
Edit
2
Std_u8
Edit
1
Std_u8
Edit
2
Std_u8
Edit
Basic documentation LMV36...
29 Parameter list LMV36...
Value range
Resolution
Min
Max
0.5 °
0,1°
0
1
1
0
1
1
0.1°
0
3
1
0
3
1
0
2
1
Default
Password level
setting
1
0
write: OEM
Index
Value
SO
0
1.7°
Password level
1
1.7°
write: OEM
1
OEM
0
OEM
1.7°
SO
Index
Value
SO
0
0
Password level
1
0
write: OEM
0
OEM
0; 0
SO
Password level
write: OEM
227/248
CC1P7544en
25.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agm60.4a9

Table of Contents