Start without prepurging (as per EN 676)

When using valve proving and 2 fuel valves of class A, prepurging is not required
(conforming to EN 676).
Prepurging can be deactivated via parameter.
No.
Parameter
Gas: Prepurging
222
0 = inactive
1 = active
Fuel 1 gas: Prepurging
322
0 = inactive
1 = active
When prepurging is activated, it is performed in accordance with the adjusted prepurge
time.
If not activated, it is nevertheless performed of the following conditions apply:
Alterable lockout position
After an off time of >24 hours
In the event of a power failure (power-on)
In the event of shutdown due to an interruption of gas supply (safety shutdown)
No.
Parameter
225
Gas: Prepurge time
325
Fuel 1 gas: Prepurge time
Basic documentation LMV36...
7 Basic unit
73/248
CC1P7544en
25.09.2013