Program stop function

To simplify the burner settings in connection with commissioning and service work, the
program sequence of the LMV36... can be stopped at the following positions:
1) Air damper in prepurge position
2) Ignition position
3) Interval 1
4) Interval 2
The program stops are integrated in the setting sequence when the plant is
commissioned (refer to chapter Air-fuel ratio curves – settings and commissioning).
After the initial settings, program stops can be activated on the parameter level.
No.
Parameter
Program stop
0 = inactive
1 = PrePurgP (Ph24)
208
2 = IgnitPos (Ph36)
3 = interval 1 (Ph44)
4 = interval 2 (Ph52)
The program stop function is maintained until manually deactivated. If the system halts
at one of the program stops, a message appears on the display of the AZL2....
Example: C:204 alternating with d:24 corresponding to program stop in prepurge
position.
Figure 41: Message in the case of program stop
7.5.5.8.
Forced intermittent operation (<24 hours)
When forced intermittent operation is activated, the unit shuts down for a moment
after 23 hours and 45 minutes of uninterrupted operation, shutdown and followed by an
automatic restart.
Forced intermittent operation is a standard feature.
No.
Parameter
239
Gas: Forced intermittent operation
0 = inactive
1 = active
279
Oil: Forced intermittent operation
0 = inactive
1 = active
339
Fuel 1 gas. Forced intermittent operation
0 = inactive
1 = active
379
Fuel 1 oil: Forced intermittent operation
0 = inactive
1 = active
7.5.5.9.

Low-fire shutdown

To prevent the boiler from being shut down under full or nearly full load conditions,
electronic air-fuel ratio control can run the burner to the low-fire position first when there
is no more request for heat (refer to chapter End of operating position).