11.3.5 Limitation of modulation range

If the modulation range shall be further restricted from 20 to 100% against the defined
curve, 4 parameters are available to define a new low-fire and high-fire position.
No.
Parameter
Lower output limit
545
undefined = 20 %
Fuel 1: Lower output limit
565
undefined = 20 %
546
Upper output limit
undefined = 100 %
566
Fuel 1: Upper output limit
undefined = 100 %
Figure 75: Restriction of modulation range
Basic documentation LMV36...
11 Electronic fuel-air ratio control
VSD
CC1P7544en
25.09.2013