4.5.1 Terminal output Inputs

Status input: Fuel selection, pressure switch
Input currents and input voltages
- UeMax
- UeMin
- IeMax
- IeMin
Contact material recommendation
for external switching contact,
transducer (Pmax, POC)
Transition / settling behavior /
bounce
- Perm. bounce time of contacts
when switching on/off
UN
Voltage detection
- On
- Off

4.5.2 Terminal output Outputs

Total contact output:
Rated voltage
Refer also Total contact output in chapter Terminal output Outputs
Individual contact loads:
Fuel valve
Rated voltage
Rated current
Power factor
Safety valve (SV)
(magnetic clutch / oil pump)
Rated voltage
Rated current
Power factor
Connections for pressure switch
Rated voltage
Rated current
Power factor
Power supply for pressure switch-max
(Pmax) / POC
(X5-02 pin 3 or X22-02 pin 3)
IaMax
Fuel feedback to LMV36...
(X31-02 pin 1 or X31-02 pin 2)
IaMax
Basic documentation LMV36...
4 Technical data
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
Gold-plated silver contacts
Max. 50 ms
(after the bounce time, the contact must
stay closed or open)
AC 120 V
AC 90...132 V
<AC 40 V
AC 120 V, 50/60 Hz
AC 120 V, 50/60 Hz
1.6 pilot duty output declaration to UL732
Cos >0.4
AC 120 V, 50/60 Hz
1.6 A pilot duty output declaration to
UL732
Cos >0.4
AC 120 V , 50/60 Hz
1.5 mA
---
<10 mA
<10 mA
37/248
CC1P7544en
25.09.2013