Oil Burner Controls
Microcontroller-based oil burner controls for the startup, supervision and control
of forced draft oil burners in intermittent operation. Standard versions with an oil
throughput up to 30 kg / h, special versions above 30 kg / h.
The LMO14..., LMO24..., LMO44... and this Data Sheet are intended for use by
OEMs which integrate the burner controls in their products.
The LMO... are designed for the startup and supervision of 1- or 2-stage forced draft oil
burners in intermittent operation. Yellow-burning flames are supervised with photo
resistive detectors QRB..., blue-burning flames with blue-flame detectors QRC...
In terms of housing dimensions, electrical connections and flame detectors, the LMO...
are identical with the LOA... oil burner controls.
Oil burners with fans to EN 267
-
Burner controls for use with atomization oil burners of monoblock design to
-
DIN EN 230:2005-10
LMO44... for use with stationary direct-fired air heaters
-
-
Electrical remote reset
-
Bridging contact for oil preheater
-
Monitoring of time for oil preheater
-
Accurate and reproducible control sequence thanks to digital signal handling
-
-
Limitation of the number of repetitions
-
Multicolor indication of fault status and operational status messages
-
LMO14...
LMO24...
LMO44...
Building Technologies Division
Infrastructure & Cities Sector
7
130
Need help?
Do you have a question about the LMO14 Series and is the answer not in the manual?
Questions and answers
Burner is off but fuel and water pump runn6
In the Siemens LMO14 Series, if the burner is off while the fuel and water pump are running, possible causes include:
- Flame detector is darkened or there is no flame signal detected, preventing burner ignition.
- The oil preheater's release contact has not closed within 10 minutes, causing a lockout.
- The control is in a lockout state due to an earlier fault; in this case, the red LED signal lamp will be lit.
- Low mains voltage (below AC 165 V for 230 V systems or AC 75 V for 120 V systems) triggering a safety shutdown.
- The burner is in a controlled shutdown due to exceeding the 24-hour continuous operation limit.
These conditions prevent burner operation even if other components are running.