12.3.1
Reference run
Different reference runs are made to unambiguously determine the actuators'
permissible working range. This means that, in the event of a power failure during
referencing, the actuator is prevented from travelling to a range outside the optical
feedback system or from running against a mechanical stop. Parameters 611 and 612
must be set, depending on the mechanical design and the type of actuator used.
In the case of reference travel type 1 the SQM33 actuator first travels to the starting
point.
Note!
Always select reference travel type 2 for SQN13 and SQN14.
No.
Parameter
611
Type of referencing
Index 0 = Fuel
Index 1 = Air
612
Fuel 1: Type of referencing for fuel
actuator
No.
Parameter
611
Type of referencing
Index 0 = Fuel
Index 1 = Air
612
Fuel 1: Type of referencing for fuel
actuator
To prevent the actuator from running against a mechanical stop during referencing, the
home position may have to be adjusted (depending on the direction of rotation and a
reference point of about 3° or 87°). In the case of stops within the usable range, the
prepurge or postpurge position must be checked also.
Refer to the figure below for details of the reference travel.