Siemens LMV36.520A1 Basic Documentation page 207

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

>3 s
If it is not only the current curvepoint that shall be changed, but all other points in the direction of travel as
well, a new straight line from the current point to P9 (press
a long push on
Display CALC
Building Technologies Division
Infrastructure & Citiies Sector
P
or
.
Example of presentation
CALC -
Figure 100: Changing several curvepoints
Note
Due to interpolation, a number of curvepoints change. The curvepoints
changed must be approached while using the warm settings to be able to
make a check on the burner. If these points have not yet been completely
approached, the normal display of the AZL2... shows OFF UPr 0 / OFF
UPr1.
Basic documentation LMV36...
28 Parameter level
V
h min s
%
) or P1 (press
P5 up to P9
CALC +
Keep
depressed for >3 s
P5 down to P1
Keep
depressed for >3 s
>3 s
) can be calculated by
207/248
CC1P7544en
25.09.2013