Siemens LMV36.520A1 Basic Documentation page 127

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Building Technologies Division
Infrastructure & Citiies Sector
No.
Parameter
Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
606
Index 1 = air
Greatest position error where an error is securely detected
 error detection band: (parameter 606 -0.6°) up to parameter 606
Fuel 1: Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
610
Index 1 = air
Greatest position error where an error is securely detected
 error detection band: (parameter 606 -0.6°) up to parameter 606
Error
Diagnostic
code
code
86
0
87
0
Basic documentation LMV36...
12 Actuators X53 / X54
Meaning for the LMV36... system
Fuel actuator: Position error
Air actuator: Position error
127/248
CC1P7544en
25.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agm60.4a9

Table of Contents