Siemens LMV36.520A1 Basic Documentation page 235

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Error
Diagnostic code
code
1
2
81
1
82
#
1
2
3
4
5
6
Building Technologies Division
Infrastructure & Citiies Sector
Meaning for the LMV36... system
Control range limitation at the bottom
Control range limitation at the top
Interrupt limitation speed input
Error during VSD's speed standardization
Timeout of standardization (VSD ramp down time too long)
Storage of standardized speed not successful
Line interruption speed sensor
Speed variation / VSD ramp up time too long / speed below
minimum limit for standardization
Wrong direction of rotation
Unplausible sensor signals
Basic documentation LMV36...
30 Error code list
Remedy
1. Basic unit is not standardized for this motor  repeat standardization.
Caution!
Settings of fuel-air ratio control must be checked!
2. Ramp time settings of the VSD are not shorter than those of the basic unit (parameters 522,
523) or the setting for the modulating operating ramp is incorrect (parameter 544)
3. Characteristic of the VSD is not linear. Configuration of the voltage input at the VSD must
accord with that of the basic unit (parameter 645).
4. VSD does not follow quickly enough the changes of the basic unit. Check settings of the VSD
(input filter, slippage compensation, hiding different speeds)
VSD speed was too high
VSD speed was too low
Too much electromagnetic interference on the sensor line
 improve EMC
Timeout at the end of standardization during ramp down of the VSD
 Ramp time settings of the VSD are not shorter than those of the basic unit (parameter: 523)
Error during storage of the standardized speed
 lock the basic unit, then reset it and repeat the standardization
Basic unit receives no pulses from the speed sensor:
1. Motor does not turn.
2. Speed sensor is not connected.
3. Speed sensor is not activated by the sensor disk (check distance)
Motor has not reached a stable speed after ramp up.
1. Ramp time settings of the VSD are not shorter than those of the basic unit (parameters 522,
523).
2. Characteristic of the VSD is not linear. Configuration of the voltage input at the VSD must
accord with that of the basic unit (parameter 645).
3. VSD does not follow quickly enough the changes of the basic unit. Check settings of the VSD
(input filter, slippage compensation, hiding different speeds)
4. Speed of VSD lies below the minimum for standardization (650 1/min)
Motor's direction of rotation is wrong.
1. Motor turns indeed in the wrong direction
 change parameterization of the direction of rotation or interchange 2 live conductors.
2. Sensor disk is fitted the wrong way
 turn the sensor disk.
The required pulse pattern (60°, 120°, 180°) has not been correctly identified.
1. Speed sensor does not detect all tappets of the sensor disk
235/248
CC1P7544en
25.09.2013