Siemens LMV36.520A1 Basic Documentation page 240

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Error
Diagnostic code
code
98
#
2 Safety valve
3 Ignition transformer
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
99
#
3
100
#
105
#
0 Pressure switch-min
1 Pressure switch-max / POC
2 Pressure switch valve proving
3 Air pressure
4 Fuel selection Fuel 1
5 Load controller on / off
6 Fuel selection Fuel 0
7 Safety loop / Burner flange
8 Safety valve
9 Ignition transformer
10 Fuel valve 1
11 Fuel valve 2
12 Fuel valve 3
13 Reset
106
#
107
#
108
#
110
#
111
#
112
0
240/248
Building Technologies Division
Infrastructure & Citiies Sector
Meaning for the LMV36... system
Error relay supervision
Relay does not pull in
Internal error relay control
Internal error relay control
Internal error relay control
Internal error contact sampling
Stuck-At failure
Internal error contact request
Internal error contact request
Internal error contact request
Internal error voltage monitor test
Power failure
Mains voltage recovery
Basic documentation LMV36...
30 Error code list
Remedy
2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral
conductor allowed.
If one of the 2 tests fails, release the unit since contacts have definitively welded and safety can no
longer be ensured.
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset. If error occurs repeatedly, replace the unit
Software version V03.10: If error C:99 D:3 occurs during standardization of the VSD, deactivate
temporarily function Alarm in case of start prevention (parameter 210 = 0, when using a release
contact) or interrupt the controller-ON signal
Make a reset; if error occurs repeatedly, replace the unit
Can be caused by capacitive loads or supply of DC voltage to the mains voltage inputs. The
diagnostic code indicates the input where the problem occurred
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Mains voltage to low
Exchange ratio diagnostics code  voltage value (120 V: 0.843)
Error code for triggering a reset on power restoration (no error)
CC1P7544en