19 PC software ACS410

The ACS410 PC software serves primarily as an operating module for the LMV36...
system, providing the following basic functions:
Visualization of system state via the following data:
- Parameters
- Process data
Configuration and parameterization of the basic unit (individual parameters)
Backup and recovery of parameter sets
Note
For notes on operation and commissioning, refer to chapter Operation.
Figure 91: Communication with display / BCI (RJ11 jack) (X56)
LMV...
Vx
TXD0
RXD0
GND
BCI
X56
CO
Bild 340/0309
Figure 92: Display input / BCI (RJ11 jack) X56
If communication between the LMV36... and the ACS410 (70 seconds) has broken
down, the password level is reset to Info / Service.
Caution!
Interruption of communication between the LMV36... and the ACS410
(30 seconds) during the time the curves are set leads to lockout!
Error-
Diagnostic
Meaning for the LMV36... system
code
code
167
9
Manual locking by the PC software
Communication breakdown
Basic documentation LMV36...
19 PC software ACS410
Bild 346/0409