Parameter Description
16-96 Maintenance Word
Range:
Function:
0
[0 -
Readout of the Preventive Maintenance
4294967295 ]
Word. The bits reflect the status for the
*
programmed Preventive Maintenance Events
in parameter group 23-1*. 13 bits represent
combinations of all the possible items:
•
Bit 0: Motor bearings
•
Bit 1: Pump bearings
•
Bit 2: Fan bearings
•
Bit 3: Valve
•
Bit 4: Pressure transmitter
•
Bit 5: Flow transmitter
•
Bit 6: Temperature transmitter
•
Bit 7: Pump seals
•
Bit 8: Fan belt
•
Bit 9: Filter
•
Bit 10: Drive cooling fan
•
Bit 11: Drive system health check
•
Bit 12: Warranty
•
Bit 13: Maintenance Text 0
•
Bit 14: Maintenance Text 1
•
Bit 15: Maintenance Text 2
•
Bit 16: Maintenance Text 3
•
Bit 17: Maintenance Text 4
®
VLT
AQUA Drive Programming Guide
16-96 Maintenance Word
Range:
®
MG20O602 - VLT
is a registered Danfoss trademark
Function:
Positio
Valve
Fan
Pump
n 4⇒
bea-
bea-
rings
rings
Positio
Pump
Tempe-
Flow
n 3 ⇒
seals
rature
trans-
transmi
mitter
tter
Positio
Drive
Drive
Filter
n 2 ⇒
system
cooling
health
fan
check
Positio
n 1⇒
0
-
-
-
hex
1
-
-
-
hex
2
-
-
+
hex
3
-
-
+
hex
4
-
+
-
hex
5
-
+
-
hex
6
-
+
+
hex
7
-
+
+
hex
8
+
-
-
hex
9
+
-
-
hex
A
+
-
+
hex
B
+
-
+
hex
C
+
+
-
hex
D
+
+
-
hex
E
+
+
+
hex
F
+
+
+
hex
Table 3.24
Example:
The Preventive Maintenance Word shows
040Ahex.
Position
1
2
3
hex-value
0
4
0
Table 3.25
The first digit 0 indicates that no items from
the fourth row requires maintenance
The second digit 4 refers to the third row
indicating that the Drive Cooling Fan requires
maintenance
The third digit 0 indicates that no items from
the second row requires maintenance
The fourth digit A refers to the top row
indicating that the Valve and the Pump
Bearings require maintenance
Motor
bea-
rings
3
3
Pressur
e
transmi
tter
Fan
belt
Warrant
y
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
4
A
123
Need help?
Do you have a question about the VLT AQUA Drive FC 200 and is the answer not in the manual?
Questions and answers