Parameters 15-** Frequency Converter Information - Danfoss VLT AQUA Drive FC 200 Programming Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description
3.14 Parameters 15-** Frequency Converter
Information
Parameter group containing frequency converter
information such as operating data, hardware configu-
ration and software versions.
3
3
3.14.1 15-0* Operating Data
15-00 Operating Hours
Range:
0 h
[0 - 2147483647 h] View how many hours the frequency
*
15-01 Running Hours
Range:
0 h
[0 - 2147483647
*
h]
15-02 kWh Counter
Range:
0 kWh
[0 - 2147483647
*
kWh]
15-03 Power Up's
Range:
0
[0 - 2147483647 ] View the number of times the frequency
*
15-04 Over Temp's
Range:
0
[0 - 65535 ] View the number of frequency converter
*
15-05 Over Volt's
Range:
0
[0 - 65535 ] View the number of frequency converter
*
15-06 Reset kWh Counter
Option:
[0]
Do not reset
*
[1]
Reset counter Select [1] Reset and press [OK] to reset the
112
VLT
Function:
converter has run. The value is saved
when the frequency converter is
turned off.
Function:
View how many hours the motor has
run. Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the frequency converter is
turned off.
Function:
Registering the power consumption
of the motor as a mean value over
one hour. Reset the counter in
15-06 Reset kWh Counter.
Function:
converter has been powered up.
Function:
temperature faults which have occurred.
Function:
overvoltages which have occurred.
Function:
Select [0] Do not reset if no reset of the kWh
counter is desired.
kWh counter to zero (see 15-02 kWh
Counter).
MG20O602 - VLT
®
AQUA Drive Programming Guide
NOTE
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option:
[0]
Do not reset
*
[1]
Reset counter Select [1] Reset counter and press [OK] to
15-08 Number of Starts
Range:
0
[0 - 2147483647 ] This is a read out parameter only. The
*
NOTE
This parameter will be reset when resetting 15-07 Reset
Running Hours Counter.
3.14.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources (15-10 Logging Source) at individual rates
(15-11 Logging Interval). A trigger event (15-12 Trigger
Event) and window (15-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
[0]
None
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference [%]
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
®
is a registered Danfoss trademark
Function:
Select [0] Do not reset if no reset of the
Running Hours counter is desired.
reset the Running Hours counter
(15-01 Running Hours) and 15-08 Number of
Starts to zero (see also 15-01 Running Hours).
Function:
counter shows the numbers of starts
and stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
Function:
Select which variables are to be
logged.