Parameter Description
16-49 Current Fault Source
Range:
0
[0 - 8 ] Value indicates source of current fault, including:
*
3
3
After a short circuit alarm (I
or phase imbalance) this will contain the power card
number associated with the alarm. It only holds one
number so it will indicate the highest priority power card
number (master first). The value will persist on power
cycle, but if a new alarm occurs it will be overwritten with
the new power card number (even if it a lower priority
number). The value will only be cleared when the alarm
log is cleared (i.e. a 3-finger reset would reset the readout
to 0).
3.15.3 16-5* Ref. & Feedb.
16-50 External Reference
Range:
0.0
[-200.0 -
*
200.0 ]
16-52 Feedback [Unit]
Range:
0.000
ProcessCtrlUnit
16-53 Digi Pot Reference
Range:
0.00
[-200.00 - 200.00 ] View the contribution of the Digital
*
16-54 Feedback 1 [Unit]
Range:
0.000
ProcessCtrlUnit
120
Function:
short circuit, over current and phase imbalance
(from left): [1-4] Inverter, [5-8] Rectifier, [0] No fault
recorded
) or overcurrent alarm (I
max2
Function:
View the total reference, the sum of
digital, analog, preset, bus and freeze
references, plus catch-up and slow-down.
Function:
[-999999.999 -
View value of resulting
999999.999
feedback value after
*
ProcessCtrlUnit]
processing of Feedback 1-3
(see 16-54 Feedback 1 [Unit],
16-55 Feedback 2 [Unit] and
16-56 Feedback 3 [Unit]) in
the feedback manager.
See parameter group 20-0*
Feedback.
The value is limited by
settings in and . Units as set
in 20-12 Reference/Feedback
Unit.
Function:
Potentiometer to the actual
reference.
Function:
[-999999.999 -
View value of
999999.999
Feedback 1, see
*
ProcessCtrlUnit]
parameter group
20-0* Feedback.
MG20O602 - VLT
®
VLT
AQUA Drive Programming Guide
16-55 Feedback 2 [Unit]
Range:
0.000
ProcessCtrlUnit
max1
16-56 Feedback 3 [Unit]
Range:
0.000
ProcessCtrlUnit
16-58 PID Output [%]
Range:
0.0 %
*
16-59 Adjusted Setpoint
Range:
0.000 ProcessCtrlUnit
3.15.4 16-6* Inputs and Outputs
16-60 Digital Input
Range:
0
[0 -
*
65535 ]
®
is a registered Danfoss trademark
Function:
[-999999.999 -
View value of Feedback 2,
999999.999
see parameter group 20-0*
*
ProcessCtrlUnit]
Feedback.
The value is limited by
settings in 20-13 Minimum
Reference/Feedb. and
20-14 Maximum Reference/
Feedb.. Units as set in
20-12 Reference/Feedback
Unit.
[-999999.999 -
999999.999
*
ProcessCtrlUnit]
Function:
[0.0 - 100.0 %] This parameter returns the Drive Closed
Loop PID controller output value in
percent.
[-999999.999 - 999999.999
*
ProcessCtrlUnit]
Function:
View the signal states from the active digital
inputs. Input 18 corresponds for example to bit
5. '0' = NO signal, '1' = connected signal.
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/2
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/4
Bit 10-63
Reserved for future terminals
Table 3.21
Function:
View value of
Feedback 3, see
parameter group
20-0* Feedback.
Function: