Parameter Description
0-61 Access to Main Menu w/o Password
Option:
[0]
Full access
*
[1]
LCP: Read only Prevent unauthorized editing of Main Menu
3
3
[2]
LCP: No access Prevent unauthorized viewing and editing
[3]
Bus: Read only
[4]
Bus: No access
[5]
All: Read only
[6]
All: No access
If [0] Full access is selected then 0-60 Main Menu Password,
0-65 Personal Menu Password and 0-66 Access to Personal
Menu w/o Password will be ignored.
0-65 Personal Menu Password
Range:
200
[0 - 999 ] Define the password for access to the My
*
0-66 Access to Personal Menu w/o Password
Option:
[0]
Full access
*
[1]
LCP: Read only Prevents unauthorized editing of My
[2]
LCP: No access Prevents unauthorized viewing and editing
[3]
Bus: Read only
[4]
Bus: No access
[5]
All: Read only
[6]
All: No access
If 0-61 Access to Main Menu w/o Password is set to [0] Full
access, this parameter will be ignored.
0-67 Bus Password Access
Range:
0
[0 - 9999 ] Writing to this parameter enables users to
*
3.2.8 0-7* Clock Settings
Set the time and date of the internal clock. The internal
clock can be used for e.g. Timed Actions, energy log, Trend
Analysis, date/time stamps on alarms, Logged data and
Preventive Maintenance.
34
VLT
Function:
Disables password defined in 0-60 Main
Menu Password.
parameters.
of Main Menu parameters.
Function:
Personal Menu via the [Quick Menu] key. If
0-66 Access to Personal Menu w/o Password is
set to [0] Full access, this parameter will be
ignored.
Function:
Disables password defined in 0-65 Personal
Menu Password.
Personal Menu parameters.
of My Personal Menu parameters.
Function:
unlock the frequency converter from bus/MCT
10 Set-up Software.
MG20O602 - VLT
®
AQUA Drive Programming Guide
It is possible to program the clock for Daylight Saving
Time/summertime, weekly working days/non-working days
including 20 exceptions (holidays etc.). Although the clock
settings can be set via the LCP, they can also be set along
with timed actions and preventative maintenance
functions using the MCT 10 Set-up Software software tool.
NOTE
The frequency converter has no back up of the clock
function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real Time
Clock module with back up is installed. If no module with
back up is installed, it is recommended the clock function
is only used if the frequency converter is integrated into
an external system using serial communications, with the
system maintaining synchronization of control equipment
clock times. In 0-79 Clock Fault it is possible to program for
a Warning in case clock has not been set properly, e.g.
after a power down.
NOTE
When mounting an Analog I/O MCB 109 option card, a
battery back-up of the date and time is included.
0-70 Date and Time
Range:
Size related
*
0-71 Date Format
Option:
[0]
YYYY-MM-DD Sets the date format to be used in the LCP.
*
[1]
DD-MM-YYYY Sets the date format to be used in the LCP.
[2]
MM/DD/YYYY Sets the date format to be used in the LCP.
0-72 Time Format
Option:
[0]
24 h
[1]
12 h
*
0-74 DST/Summertime
Option:
[0]
Off
*
[2]
Manual
®
is a registered Danfoss trademark
Function:
[ 0 - 0 ] Sets the date and time of the internal
clock. The format to be used is set in
0-71 Date Format and 0-72 Time Format.
Function:
Function:
Sets the time format to be used in the LCP.
Function:
Choose how Daylight Saving Time/Summertime
should be handled. For manual DST/Summertime
enter the start date and end date in 0-76 DST/
Summertime Start and 0-77 DST/Summertime End.