Parameters 30-** Special Features; Parameters 31-** Bypass Option - Danfoss VLT AQUA Drive FC 200 Programming Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description

3.25 Parameters 30-** Special Features

3.25.1 30-8* Compatibility
30-81 Brake Resistor (ohm)
Range:
Size related
[ 5. - 65535.00
*
Ohm]

3.26 Parameters 31-** Bypass Option

Parameter group for the configuration of the electronically
controlled bypass option board, MCO 104.
31-00 Bypass Mode
Option:
Function:
[0]
Drive
Select the operating mode of the bypass:
*
[0] Drive: the motor is operated by the frequency
converter.
[1]
Bypass Select the operating mode of the bypass:
[1] Bypass: motor can be run at full speed in bypass
mode.
31-01 Bypass Start Time Delay
Range:
Function:
30 s
[0 - 60 s] Set the time delay within the time when the
*
bypass receives a run command and the time
when it starts the motor at full speed. A
countdown timer will display time left.
31-02 Bypass Trip Time Delay
Range:
Function:
0 s
[0 - 300
Set the time delay within the time that the
*
s]
drive experiences an alarm that stops it and the
time when the motor is automatically switched
to bypass control. If the time delay is set to
zero, a drive alarm will not automatically switch
the motor to bypass control.
31-03 Test Mode Activation
Option:
Function:
[0]
Disabled [0] Disabled means that the Test Mode is
*
disabled.
[1]
Enabled [1] Enabled means that the motor runs in bypass,
while the frequency converter can be tested in an
open circuit. In this mode the LCP will not control
start/stop of the bypass.
®
VLT
AQUA Drive Programming Guide
Function:
Set the brake resistor value in
Ohm with two decimals. This
value is used for monitoring the
power to the brake resistor in
2-13 Brake Power Monitoring.
®
MG20O602 - VLT
is a registered Danfoss trademark
31-10 Bypass Status Word
Range:
Function:
0
[0 - 65535 ] Views the status of the bypass as a
*
hexadecimal value.
31-11 Bypass Running Hours
Range:
Function:
0 h
[0 - 2147483647
Views the number of hours in which
*
h]
the motor has run in Bypass Mode. The
counter can be reset in 15-07 Reset
Running Hours Counter. The value is
saved, when the frequency converter is
turned off.
31-19 Remote Bypass Activation
Option:
Function:
[0]
Disabled
*
[1]
Enabled
Feature: Unknown.