Parameter Description
26-61 Terminal X42/11 Min. Scale
Range:
0.00
[0.00 -
%
200.00 %]
*
3
3
See principle graph for 6-51 Terminal 42 Output Min Scale.
26-62 Terminal X42/11 Max. Scale
Range:
100.00
[0.00 -
%
200.00
*
%]
See principle graph for 6-52 Terminal 42 Output Max Scale.
26-63 Terminal X42/11 Bus Control
Range:
0.00 %
[0.00 - 100.00 %] Holds the level of terminal X42/11 if
*
26-64 Terminal X42/11 Timeout Preset
Range:
0.00 %
[0.00 - 100.00
*
%]
180
VLT
Function:
Scale the minimum output of the selected
analog signal at terminal X42/11, as a
percentage of the maximum signal level.
E.g. if a 0 V is desired at 25% of the
maximum output value. Then programme
25%. Scaling values up to 100% can never
be higher than the corresponding setting
in 26-62 Terminal X42/11 Max. Scale.
Function:
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value
to the maximum value of the voltage signal
output. Scale the output to give a voltage
lower than 10 V at full scale; or 10 V at an
output below 100% of the maximum signal
value. If 10 V is the desired output current at a
value between 0-100% of the full-scale output,
programme the percentage value in the
parameter, i.e. 50% = 10 V. If a voltage
between 0 and 10 V is desired at maximum
output, calculate the percentage as follows:
(
)
V
10
x 100 %
desired maximum voltage
i.e.
V
10
V :
x 100 % = 200 %
5
5
V
Function:
controlled by bus.
Function:
Holds the preset level of terminal
X42/11.
In case a bus time-out and a time-out
function are selected, the output will
preset to this level.
MG20O602 - VLT
®
AQUA Drive Programming Guide
®