90
Commissioning
9.1.1.3.2 "Module Parameters" Menu Item
Various I/O module parameters can be set using this menu item:
Figure 46: "Module Parameters" Menu Item
Table 57: "Module parameters" menu item
Option
Tipp Mode
TIP Time
Activate
Target Window
Current Value
K-Bus Failure *
Enable manual
operation for:
Substitute Value Configuration
Show last value from
process image.
Show substitute value
for current.
* Function supported in software version 03 or higher.
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
Description
The time period for TIP mode can be defined.
TIP mode is activated.
TIP mode is deactivated.
This value is the tolerance threshold [in percent] for the setpoint value
entered (see "Operation" menu item).
Example: If the setpoint value = 50 % and the setting = 1 %, the target
position is reached (bit "On Target" = "1"), if the actual value is between
49 % and 51 %.
Manual mode is permitted for the respective valve.
Manual mode is not permitted for the respective valve.
The final value contained in the process image serves as the substitute
value.
The value defined in the "Substitute value, current" input field serves as
the substitute value.
WAGO I/O System 750/753
750-632 Proportional Valve Module