102 Commissioning
8.3.5
Setting Parameters
Table 47: Adjustable Parameters
Parameter name
Module parameters
Analog value data
format
Sampling frequency
Acknowledgement mode
PROFIsafe V2.4
passivation mode
Channel pair parameters
Sensor evaluation
Discrepancy time
Unit value
Tolerance window
Relative tolerance
Absolute tolerance
Manual
Version 1.0.0, valid from HW/SW Version 01/01
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Value range
Format Siemens S7 with fixed substitute values
Format Siemens S7 with parameterizable substitute
values(
RIOforPA
100 Hz
60 Hz
50 Hz*
10 Hz
Module-internal
Module-external*
Channel granularity
Module-wide*
Single-channel*
Two-channel
5 ... 65535 ms (100 ms*)
Min*
Max
Relative
Absolute
Absolute + relative*
±0.2 ... ±20 % (2 %*)
±0.2 ... ±20 % (2 %*)
WAGO-I/O-SYSTEM 750