● Empty lines are not permitted (an empty line will be interpreted as the end of the list).
● No distinction is made between upper-case and lower-case letters.
● It does not matter whether you use "\" or "/" in the path name.
6.2.4

Restoring non-volatile data

Prerequisite
The diagnostic data and non-volatile data have been backed up to the CompactFlash Card.
For details, refer to the section titled Backing up diagnostic data and non-volatile data
(Page 173).
Procedure
To restore non-volatile data after a CPU has been replaced, proceed as follows:
1. Insert the CompactFlash Card into the new D410 (which must be switched off).
2. Set the switch to the "Delete non-volatile data" setting (i.e. set DIP switch S5 to ON).
Figure 6-5
D410
Commissioning Manual, 05/2009
Figure 6-4
Depiction of DIAGURLS.TXT editor
The positions of the mode selector switches are not relevant (i.e. the operating mode set
remains unchanged).
Switch position for restoring non-volatile data
Service and diagnostics
6.2 Diagnostic data and non-volatile data
179