Siemens SIMOTION D410 Series Commissioning Manual page 160

Hide thumbs Also See for SIMOTION D410 Series:
Table of Contents

Advertisement

Maintenance and service
5.4 Performing a firmware and project update
● Backing up configuration data for modular machines in conjunction with the
● Backing up unit data (data saved on the CompactFlash Card using
Re-compiling and downloading project data in SIMOTION SCOUT
Re-compile and download the project data after upgrading the D410. To do this, you have
the following options:
● Download the project to the CompactFlash Card using the SIMOTION D410
● Download the project directly to the CompactFlash Card using the CompactFlash Card
In both cases, the firmware update is performed automatically.
160
_activateConfiguration system function, stored in the following directory:
– install\simotion
_saveUnitDataSet/_exportUnitDataSet), stored in the following directory:
– user\simotion\user dir\<unitname>
Note
When a version is changed, you must use the "Back up variables" function to back up
data saved using _saveUnitDataSet or _exportUnitDataSet in a way that is not
dependent on the version. You then have the option of restoring them using "Restore
variables".
When performing an upgrade with a firmware version that is ≥ V4.1, these two
functions are only required for backing up and restoring unit data sets that have been
created using _saveUnitDataSet.
Retain and unit data (saved with _exportUnitDataSet) remain valid even after a
version upgrade.
You require an online connection between the programming device/PC and
SIMOTION D410 for this purpose. Select the "Download project to target system"
command to download the project to SIMOTION D410. The connection to the SINAMICS
Integrated is automatically established.
For details, refer to the section titled Downloading a project created offline to the target
system (Page 70).
adapter
You can use a card reader to write the entire project to the CompactFlash Card, even
while offline. In SIMOTION SCOUT, you can call the "Download to the file system"
function in the context menu of the SIMOTION device.
For details, refer to the section titled Loading a project created offline to the
CompactFlash Card (Page 71).