Siemens SIMOTION D410 Series Commissioning Manual page 135

Hide thumbs Also See for SIMOTION D410 Series:
Table of Contents

Advertisement

Restoring the default settings using the DIL switch
1. The power supply is shut down.
2. Select the MRES operating mode by
Figure 4-41
3. Restart the power supply.
4. Change to the required mode by setting the DIL switch.
D410
Commissioning Manual, 05/2009
– Setting mode selector switches S1 to S3 to OFF AND
– Using the service selector switches to ensure that no service functions are selected
(S4 to S7 = OFF).
(See figure below.)
MRES switch position
The FRAM and the user data are deleted. The default settings are loaded. SIMOTION
D410 remains in STOP mode.
Note
The default communications parameters are now restored. You must re-configure the
communication parameters of SIMOTION D410.
Commissioning (software)
4.14 Deleting data
135