Siemens SIMOTION D410 Series Commissioning Manual page 87

Hide thumbs Also See for SIMOTION D410 Series:
Table of Contents

Advertisement

3. Click "Assume control priority". The "Assume Control Priority" dialog box opens.
4. Read the notes and confirm these with "Accept".
5. Activate the "Enables" checkbox to enable the drive.
6. Enter your setpoint in the input field and shift the scaling to 0% as safety setting.
Figure 4-19
Entering the setpoint
7. Click the "Drive On" button. The "Enable is set" LED lights up in green color. The drive
8. Click "Drive Off" to stop the drive after you completed the test.
9. Deactivate the enable signal and click "Give up control priority" to deactivate controlling at
D410
Commissioning Manual, 05/2009
Figure 4-18
Assuming control priority
All enables are now set with the exception of ON/OFF1.
starts moving as you move the slider towards the right side. The current motor speed is
displayed in "Actual".
the programming device / PC.
4.5 Testing the configured drive using the drive control panel
Commissioning (software)
87