Commissioning (software)
4.14 Deleting data
Memory reset using the mode selector switch
The mode selector switch function is implemented in SIMOTION D410 by means of a DIL
switch (DIL = Dual-In-Line). Use this DIL switch (switch S1 - S3) to set the binary code for
the mode of operation.
Information pertaining to to the switch positions and corresponding modes of operation is
available in the
You can only reset memory using the mode selector switch if SIMOTION D410 is operating
in offline mode.
How to reset the memory:
1. Select the MRES operating mode by
Figure 4-40
2. Set switch 1 to ON (STOP mode) once the RUN/STOP LED permanently lights up yellow.
3. Within 3 seconds, set the switch back to MRES operating mode by setting switch S1 to
132
SIMOTION D410
– Setting mode selector switches S1 to S3 to OFF AND
– Using the service selector switch to ensure that no service functions are selected (S4
to S7 = OFF).
The RUN/STOP LED will begin flashing soon after this (slowly flashing yellow).
Switch position MRES
OFF again. The memory reset is performed (the RUN/STOP LED flashes yellow quickly).
Manual.
D410
Commissioning Manual, 05/2009