Maintenance
9.1
Backing up and restoring data
Introduction
The operating system and the Runtime software are located on the supplied Restore DVD.
You can use this to restore the original software of the CPU 1515SP PC (F).
If you use functions from the Restore menu, you must acknowledge a security message. For
the functions, 72 hours are available in each case. If the functions are no completed within
this period, the CPU 1515SP PC (F) is automatically restarted.
Save your project to partition D: of the CFast card.
SIMATIC IPC Image & Partition Creator
You can also create your own image of your CFast card. This contains the operating system,
the Runtime software and the complete project loaded from the TIA Portal.
To back up data in Windows Embedded Standard 7, we recommend the software tool
SIMATIC IPC Image & Partition Creator (V3.3 or later). It provides for easy backup and fast
restore of the contents of the CFAST card and of individual partitions (images).
Note
The SIMATIC Image & Partition Creator supports the X2 PN/IE (LAN) interface.
You can procure the SIMATIC IPC Image & Partition Creator:
● via the Siemens online ordering system (http://www.siemens.com/automation/mall).
● Pre-installed on the SIMATIC IPC Service USB flash drives.
For additional information, please refer to the corresponding product documentation.
SIMATIC IPC Service USB flash drive
You can use the SIMATIC IPC Service USB flash drives for data backup and restore.
You obtain these through the Siemens online ordering system
(http://www.siemens.com/automation/mall).
84
9
CPU 1515SP PC (F)
Manual, 05/2017, A5E32701806-AC