CIMR-F7Z Varispeed F7 The industrial workhorse • Flux vector control with or without PG • Silent operation. No current de-rating in silent mode. • Torque control • PID control • Powerful application oriented functionality • Stand still autotuning • High slip braking •...
322 A in case of heavy duty mode When using the inverter of 200 V class 37 kW or more with a cooling fan of three-phase 230 V 50 Hz or 240 V 50/60 Hz power supply, a transformer for the cooling fan is required.
Available as standard enclosed type Model CIMR-F7Z 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300 Enclosed type - IP20 Available as standard Available for option...
Page 4
Voltage output kW CIMR-F7Z weight kg method ------ 0.75 ------ ------ ------ ------ Not available, please use the IP20 type removing the upper and lower cover ------ ------ ------ ------ 18.5 ------ 2022 0 2030 0 2037 0 2045 0 12.5...
Page 5
Enclosed type (IEC IP20) F7Z 20P41 to F7Z25P51 F7Z 27P51 to F7Z20181 F7Z 20221 to F7Z20751 F7Z40P41 to F7Z45P51 F7Z47P51 to F7Z40181 F7Z40221 to F7Z41601 Fig 1 Fig 2 Fig 3 Dimensions in mm Max. applicable motor Inverter Approx. Cooling...
Page 6
3G3RV-PFI2100-SE 3G3RV-PFI3010-SE 3G3RV-PFI3018-SE 3G3RV-PFI3021-SE 3G3RV-PFI3035-SE 400 V 3G3RV-PFI3060-SE 32.5 12.0 3G3RV-PFI3410-SE 12.0 3G3RV-PFI3600-SE 3G3RV-PFI3800-SE Flat filters are not possible to be mounted as footprint filters. Bookform filters Dimensions Model 3G3RV-PFI2130-SE 200 V 3G3RV-PFI2160-SE 3G3RV-PFI2200-SE 3G3RV-PFI3070-SE 3G3RV-PFI3100-SE 400 V 3G3RV-PFI3130-SE 3G3RV-PFI3170-SE...
Braking unit Model CDBR-2015 B, -2022 B, -4030B, -4045 B Model CDBR-2110 B 4-M6 MTG holes 4-M4 MTG holes 66.5 Main circuit terminal Lead wire inlet (28 dia. rubber bush) 2-lead wire inlet (35 dia. rubber bush) 114.5 30 or...
Page 8
Heatsink external mounting attachment The Varispeed G7 inverters under the 200/400 V class 15 kW or less need this attachment for mounting the heatsink externally. This attachment expands the outer dimensions of the width and height of the inverter. (Attachment is not required for inverters of 18.5 kW or more.)
20 k Multi-function analog output 1 Analog input 1: Master 0 to 10 V (-10 to +10 V 2 mA / 4 to 20 mA) frequency reference [Default: Output frequency 0 to +10 V] 0 to +10V (20 k )
Cooling fan power supply r/ : 200 to 220 VAC 50 Hz, 200 to 230 VAC 60 Hz (A transformer is required for 230 V 50 Hz or 240 V 50/60 Hz power supply.) Cooling fan power supply r/ 200 /...
Page 11
– – The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1 for S6 and multi-step speed setting 2 for S7. Do not use this power supply for supplying any external equipment.
Fan cooled 400 V class Model CIMR-F7Z 40P4 40P7 41P5 42P2 43P7 44P0 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300 Inverter capacity 110 140 160 200 230 280 390 510 Rated current 8.0 12.5 17...
Page 13
AC reactor Application example Connection example Power supply AC reactor capacity (kVA) MCCB Motor AC Reactor required for power supply harmonics Varispeed F7 AC reactor not required Inverter capacity (kVA) 200 V class 400 V class Max. applicable Current value Inductance Max.
Fuse installation To protect the inverter, it is recommended to use semiconductor fuses as shown in the table below FUSE Inverter type Voltage (V) Current (A) t (A 20P4 12~25 20P7 12~25 21P5 23~55 22P2 34~98 23P7 82~220 25P5 220~610...
Ordering information 3G3IV-PCN329-E 3G3IV-PCN126/326 CX-Drive JVOP-160 OY JVOP-161-OY Inverter to PC cable Digital operator Digital operator Digital operator extension cable (LCD display) (LED display) Line filter Braking accessories Varispeed Feedback speed option card Communication option cards Reference option card PLC option card...
Page 16
• PG frequency range: Approx. 300 kHz max. [Power supply output for PG: +5 V or +12 V, max. current 200 mA] • Pulse monitor output: RS-422 • Dual channel encoder: 1st channel A, B, Z / 2nd channel A, B, Z or open collector. Frequency inverters...
Page 17
Communication option cards Type Model Description Function • Used for running or stopping the inverter, setting or referencing parameters, and monitoring 3G3RV-PDRT2 DeviceNet option card output frequency, output current, or similar items through DeviceNet communication with the host controller. • Used for running or stopping the inverter, setting or referencing parameters, and monitoring...
Page 18
7 segment LED digital operator (60) Panel cutout installation 3G3IV-PCN126 Digital operator extension cable 3G3IV-PCN326 1 meter Extension cable to connect inverter and digital operator. 3 meters 3G3IV-PCN329-E PC configuration cable Cable to connect the inverter to PC. Computer software Type...
Page 19
For an application with large regenerative power such as hoisting, the braking torque or other items may exceed the capacity of a braking unit with a braking resistor in a standard combination (an result in capacity overload). Contact your OMRON representatives when the braking torque or any other item exceeds the values in the table.
Page 20
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. Cat. No. I23E-EN-02 Frequency inverters...
Need help?
Do you have a question about the VARISPEED F7 and is the answer not in the manual?
Questions and answers