CAUTION:
If using your own cable, make sure you use the proper connections.
To insert wires into the terminal block that serves three PSMs:
a. Insert the grounding wire into the grounding point labeled GND.
b. Insert the wire labeled L1 into the input terminal labeled A2.
c. Insert the wire labeled L2 into the input terminal labeled B2.
d. Insert the wire labeled L3 into the input terminal labeled C2.
e. Insert the wire labeled N into the input terminal labeled N2.
WARNING:
by mis-wired PDMs, before reinstalling the metal cover to the wiring
compartment, apply AC voltage to the PDM (with disengaged PSM) to make
sure that two LEDs on the PDM are lit green and that the AC voltage between
AC terminal blocks A1-N1, B1-N1, C1-N1, A2-N2, B2-N2, and C2-N2 for
three-phase wye PDM is not more than 264 VAC when measured with a digital
voltage meter (DVM). Then turn off the AC breaker de-energizing the PDM and
install the metal cover and engage all AC PSMs.
NOTE:
The terminal connections have either slotted screws or hex screws. Use a 1/4-in.
slotted screwdriver for the slotted screws. Use a 5/32-in. (4 mm) Allen wrench for the
5/16-in. hex screws.
NOTE:
Three-phase wye AC wire assembly kits can be purchased from Juniper Networks.
Table 93: Supported Three-Phase Wye AC Wire Gauge
Wire Gauge
5 x 10-AWG or equivalent
Wire label configuration is for Juniper Networks supplied cable only.
To protect power supplies from input voltage that might be caused
Description
5 conductor wires, each wire is 10-AWG
421