d. Nominal value of line current is 28 A.
e. Current rating for input 1 is 28 A.
f. Only one AC PSM is connected between two lines and neutral.
g. Nominal value of input current for one AC PSM is 2800 W / 200 V = 14 A.
h. Nominal value of line current is 14 A.
i. Current rating for input 2 is 14 A.
5. Calculate thermal output (BTUs). Multiply the input power requirement (in watts) by 3.41 as shown in
Table 63 on page
184.
Table 63: Calculating AC Thermal Output
Power Distribution Module
MX2010 three-phase delta AC PDM
MX2010 three-phase wye AC PDM
RELATED DOCUMENTATION
MX2010 Power System Description | 95
MX2010 AC Power Requirements | 161
Connecting AC Power to an MX2000 Router with Three-Phase Delta AC Power Distribution
Modules | 291
Thermal Output (BTUs per hour)
Maximum power divided by 0.91 * 3.41 = BTU/hr.
Input power = Maximum power divided by 0.91
Refer to
"MX2010 AC Power Requirements" on page 161
to calculate maximum power, which is dependent on
configuration and temperature.
Maximum power divided by 0.91 * 3.41 = BTU/hr.
Input power = Maximum power divided by 0.91
Refer to
"MX2010 AC Power Requirements" on page 161
to calculate maximum power, which is dependent on
configuration and temperature.