Juniper MX2010 Hardware Manual page 139

Universal routing platform
Hide thumbs Also See for MX2010:
Table of Contents

Advertisement

Figure 47: DC Power Supply Module
The DC power system is feed redundant. Each DC PSM can be connected to two separate feeds from
different sources that are used to provide feed redundancy. If two feeds are connected, PSM input power
is drawn from the feed with the higher voltage present. There are two PDMs per power system capable
of carrying nine feeds each. Connect feeds from one source to one PDM and feeds from the other source
to the second PDM of the power system. The primary input of the PSM is a dual redundant feed, INP0
and INP1. Both feeds are active during operation, but both feeds might or might not be providing current.
Move the input mode DIP switch to the on or off position to determine the power supply feeds (see
Table 38 on page 117
and
craft interface. Each PDM has an LED per feed indicating whether the feed is active or not, or whether
the feed is connected properly, see
page
201.
Table 38: DIP Switch Positions on the DC PSM
Left Switch Position
Off
On
Off
On
Figure 48 on page
118). In addition, a PSM failure triggers the alarm LED on the
"MX2010 DC Power (-48 V) System Electrical Specifications" on
Right Switch Position
Off
Off
On
On
Input Source
None
Input 0 (INP0)
Input 1 (INP1)
Both Input 0 and Input 1
117