Functions
Mechanical design
Parameter
Config save SD
Config save SD done
Config load SD
Config load SD done
136 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 136
BDCX.100820.01GB
Building Technologies
11

Save / restore parameters

– A fully configured and parameterized plant can be backed up on an SD card or
load on the controller from the card.
– Two different parameter sets for an identically configured plant can be backed
up on the controller and restored. For example, a back up after parameterizing
the standard parameters at the factory (Par factory save) and a backup after
commissioning the plant (Par service save).
The actions list below only possible with the appropriate access levels.
Main Index > System overview > Save / restore
Range
− 
− Execute
− No
− Yes
− 
− Execute
− No
− Yes
Standard application AHU
Save / restore parameters
Function
Requires access level 4.
Backs up present plant configuration with all pa-
rameters on the SD card:
− Passive position.
− Run backup. The display than returns to .
An existing parameter file (Param.bin) is
overwritten on the card.
Displays whether the configuration was success-
fully backed up on the SD card:
− Save not conducted or unsuccessful.
− Save successful. This parameter reset to No
are power outage or reset.
Requires access level 4.
Loads configuration file (Param.bin) with the
plant configuration and all parameters from the
SD card to the controller. A reset required after
download!
Caution: The Main Index > Configuration > Con-
figuration by = Download must be set prior to
fully downloading a new configuration.
− Passive position.
− Execute download. The display than returns to
.
Displays whether the configuration download
was successful:
− Download no conducted or unsuccessful.
− Download successful. This parameter reset to
No are power outage or reset. The controller
operate using the configuration loaded from
the SD card.