Parameter
Damper
Fire damper
Prerequisite
Function
Parameter
Parameter
Outside air cmd
Outside air fdbk
Outs offby fdbk alm
StrtUpDly outs fdbk
Extract air cmd
Extract air fdbk
Extr offby fdbk alm
StrtUpDly Extr fdbk
Opening time
Siemens
Building Technologies
Range
---
– On
– Off
5.3.2
Supply / Exhaust damper
Air and exhaust air dampers are enabled and preconfigured in configuration 1, con-
figuration 2 and configuration I/Os.
Per settings outside and exhaust air damper open at plant start and close at plant
stop. Damper opening times can be defined separately. A common default period
can be set if no damper feedback exists. The damper command can still be kept at
pending for a feedback alarm.
Only the output for the outside air damper is enabled if two dampers are enabled
as combined. This is also true for triggering feedback alarms for the exhaust air
damper, if a separate feedback per damper is enabled.
Outside damper is forced by the supply fan. Exhaust damper is forced by the
exhaust fan. If combined damper is selected, then the output for ouside damper is
forced by both supply fan or exhaust fan. Take care if for example Firemode
RunExh is used.
Main Index > Unit > Damper Control > Damper
Range
Off
On
No
Yes
No
Yes
0...36000 [s]
Off
On
No
Yes
No
Yes
0...36000 [s]
0...36000 [s]
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Functions
Function
Jump to damper page to parameterize the outside
and exhaust air damper.
Current fire damper status. Jump to fire damper
page to parameterize the fire damper.
Function
Current state of outside air damper command. Go
to page with all digital output settings.
Active feedback as to whether the damper is open.
Go to page with all digital input settings. For exam-
ple, you can set the time for jitter protection (De-
fault: 5 s).
Determines, in the event of a feedback fault,
whether a damper command is still pending or
whether to switch off the command.
Defines the period after an open command without
feedback before a feedback alarm is triggered. Jit-
ter time is enabled exclusively if the feedback is
pending after this period.
Current state of exhaust air damper command.
Go to page with all digital output settings.
Active feedback as to whether the damper is open.
Go to page with all digital input settings. For exam-
ple, you can set the time for jitter protection (De-
fault: 5 s).
Determines, in the event of a feedback fault,
whether a damper command is still pending or
whether to switch off the command.
Defines the period after an open command without
feedback before a feedback alarm is triggered. Jit-
ter time is enabled exclusively if the feedback is
pending after this period.
Estimates damper opening time for both dampers, if
47 / 244
CE1P3977en_02
Page 47
01.02.2010