Siemens Climatix Series Basis Document page 192

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Operating mode >Time switch program
Parameter
Function
Schedule
Only if TspFunction <= Steps
Jumpline to the Scheduler
Schedule
Only if TspFunction = Steps+Tmp
Jumpline to the Scheduler
Calendar exception
Jumpline to the Calendar
Calendar fix off
Jumpline to the Calendar Off (special
settings in Exceptions)
Main Index > Unit > Operating mode > External control
Parameter
Function
Act mode
Actual Operating Mode from External
Control
Auto = TSP
Off and Stage 1 ..Stage 3 = override from
External Unit Switch
Tmp stpt input 1
Only possible if TSP Function= Step+Temp
Start the Unit in selected Mode
Only Input 1 Enabled
Start the Unit in selected Mode with setted
Fan Step
Input 1 and 2 Enabled
if Input 1 = TRUE Start the Unit in selected
Mode with Fan Step 1
if Input 2 = TRUE Start the Unit in selected
Mode with Fan Step 2
if both Inputs are TRUE Start the Unit in
selected Mode for Input 2 with setted Fan
Step
Tmp stpt input 2
Only possible if TSP Function= Step+Temp
and External Control = Two
if Input 2 = TRUE Start the Unit in selected
Mode with Fan Step 2
if both Inputs are TRUE Start the Unit in
selected Mode for Input 2 with setted Fan
Step
Off delay
After this Time the External Control is
disabled.
If this Time is 0 the Timer function is
disabled
Fan steps
The selection of the Step and Operation
TSP Function= Step
Only Input 1 Enabled
Input1=TRUE  selected Fan Step
Input1 = False  Auto
Two Inputs Enabled
Input1 = TRUE Step1
Input2 = TRUE Step2 (only one Step
enabled St1)
Input1 and Input2 = TRUE selected Fan
Step
Input1 and Input2 = FASLE  Auto
Start/Stop Funct
Activate the Pushbutton function for the
Inputs 1 and 2
192 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 192
BDCX.100820.01GB
Building Technologies
17.12.2 Time switch program
17.12.3 External control
Standard application AHU
HMI
Value range
Unit
Off
Stage1...Stage3
Off
Eco St1...Eco St3
Comf St1...Comf St3
Passive...Active
Passive...Active
Value range
Unit
Auto
Off
Stage1...Stage3
Comfort
Economy.
Comfort
Economy.
0...23
h
Auto
Off
1Step
2Step
3Step
Off
On
Standard
R S Link
Off
X
Off
X
Section:
5.2.3
X
X
Standard
R S Link
X
Comfort
4
Comfort
4
Section:
5.2.4
0.0
4
4
Off
4
CE1P3977en_02