Prerequisite
Parameterization
Parameter
Act controlled tmp
Act cooling stpt
Act heating stpt
Act sply clg stpt
Act sply htg stpt
External setpoint
Sply air comp
Comfort setpoint
Comfort cooling
Comfort heating
Comfort deadzone
Economy setpoint
Economy cooling
Economy heating
Economy deadzone
Extra Seq setpoint
Supply tmp min stpt
Supply tmp max stpt
60 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 60
BDCX.100820.01GB
Building Technologies
5.5.2
Temperature setpoints
Displays only the functions enabled in configuration 1 or configuration 2. All other
functions are hidden.
Main Index > Unit > Temp control > Tmp setpoints
Range
---
---
---
---
---
---
-10.0...10.0 [°C]
0...99 [°C]
0...99 [°C]
0...99 [°C]
0...20 [°C]
0...99 [°C]
0...99 [°C]
0...99 [°C]
0...20 [°C]
0...99 [°C]
15.0... Supply tmp
max stpt [°C]
Supply tmp min stpt
... 50.0 [°C]
Standard application AHU
Functions
Function
Present temperature used for control.
Eight supply air, room or return temperature depending on
the setting and control type.
Present calculated room or supply air setpoint for cooling.
Present calculated room or supply air setpoint for heating.
Present calculated supply air setpoint in cooling for a cas-
cade control.
Present calculated supply air setpoint in heating for a cas-
cade control.
Present external setpoint or setpoint compensation.
Setpoint compensation for winter operation for:
Tmp control mode = RmSplyC Su (Room supply air cas-
cade control in summer, pure supply air control in winter).
or
Tmp control mode = RtSplyC Su (return supply air cas-
cade control in summer, pure supply air control in winter).
The room setpoint for cascade control, active in the sum-
mer, are active (summer - winter changeover).
During winter, these room setpoints must be adapted to
the supply air control.
Comfort based setpoint. Only available when Tmp stpt
selection = +/-Half degree Celsius.
Comfort cooling setpoint. Only available when Tmp stpt
selection = Htg/Clg or Clg-degrees Celsius.
Comfort heating setpoint. Only available when Tmp stpt
selection = Htg/Clg or Htg-degrees Celsius.
Comfort dead zone. Only available when Tmp stpt selec-
tion = Clg-degrees Celsius or Htg+degrees Celsius or +/-
Half degree Celsius.
Economy base setpoint. Only available when Tmp stpt
selection = Spv+Halfdegree Celsius.
Economy setpoint for cooling. Only available when Tmp
stpt selection = Htg/Clg or Clg-degrees Celsius.
Economy setpoint for heating. Only available when Tmp
stpt selection = Htg/Clg or Htg-degrees Celsius.
Economy dead zone. Only available when Tmp stpt selec-
tion = Clg-degrees Celsius or Htg+degrees Celsius or +/-
Half degree Celsius.
Setpoint for Heating 2, El Heating 2, Cooling 2 if config-
ured as stand alone.
Lower allowable supply air temperature for pure room or
return air control with additional available supply air sen-
sor. Limited control of the cooling setpoint occurs if the
supply air temperature < Supply tmp min. The heating reg-
ister is started if this is not enough.
Highest allowable supply air temperature for pure room or
return air control with additional available supply air sen-
CE1P3977en_02
01.02.2010