Main Index > Unit > Inputs > Pressures/Flows
Parameter
Function
Exhaust air flow
Exhaust air flow
HrecFrost Pressure
Heat recovery Frost Pressure
Main Index > Unit > Inputs > Humidity
Parameter
Function
Supply Rel
Supply Humidity relative
Room Rel
Room Humidity relative
Outside Rel
Outside Humidity relative
Main Index > Unit > Inputs > Other
Parameter
Function
AirQuality
Air Quality
ExtSetpoint
External setpoint (abslute or shifting)
Settings
Jump line to Curve settings for External
setpoint
Main Index > Unit > Inputs > Digital Inputs
Parameter
Function
Emergency stop
Emergency stop
SuWi Input
External Switch for Summer Winter change
over
Ext control input1
External Switch1 for switching the Unit
Ext control input2
External Switch2 for switching the Unit
Alarm ackn button
Alarm ackn button
FireDamper Opened
Fire damper Feedback Opened
FireDamper Closed
Fire damper Feedback Closed
SupplyDamper fdbk
Supply Damper Feedback Opened
ExhaustDamper fdbk Exhaust Damper Feedback Opened
Auxiliary input
Auxiliary input
Main Index > Unit > Inputs > Digital alarms
Parameter
Function
Fire
External Fire alarm
Fan
If combined Fan generally Fan alarm
Supply Fan
Supply Fan alarm
SupplyFan fdbk
Supply Fan Feedback (eg. Pressure Switch) OK...Fault
ExhaustFan
Exhaust fan alarm
ExhaustFan fdbk
Exhaust fan Feedback (eg. Pressure Switch)
Filter
Filter alarm (only if combined Fan)
Supply Filter
Supply Filter alarm
Exhaust Filter
Exhaust Filter alarm
Frost protect hrec
Heat recovery Frost monitor
Hrec
Heat recovery alarm
HrecPump
Heat recovery Pump alarm
HrecPump fdbk
Heat recovery Pump Feedback
Htg frost protect
Htg frost protect Detector
Heating pump
Heating pump alarm
HtgPump fdbk
Heating pump Feedback
ElHeating
Electrical Heater alarm
Humidifier fdbk
Humidification Feedback
Humidifier pump
Humidification Pump alarm
HumidifierPump fdbk Humidification Pump Feedback
CoolingDx
Dx Cooling alarm
190 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 190
BDCX.100820.01GB
Building Technologies
17.11.3 Humidity
17.11.4 Other
17.11.5 Digital inputs
17.11.6 Digital alarms
Standard application AHU
HMI
Value range
Unit
0...40000
l/s
0...5000
Pa
Value range
Unit
0...100
%rH
0...100
%rH
0...100
%rH
Value range
Unit
0...3000
ppm
-64.0...64.0
°C
Value range
Unit
On...Off
Winter...Summer
On...Off
On...Off
active...passive
OK...Fault
OK...Fault
OK...Fault
OK...Fault
On...Off
Value range
Unit
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
Standard
R S Link
x
Standard
R S Link
x
Section:
x
15.3.4
x
Standard
R S Link
x
x
Section:
15.3.7
Standard
R S Link
x
x
x
x
x
Section:
x
15.3.5
x
x
x
x
Standard
R S Link
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Section:
x
x
x
x
x
x
CE1P3977en_02
01.02.2010