Check config I/Os

Hardware assignments made in Configuration I/Os are checked using this function:
• Check whether and what points are not assigned.
• Checks whether hardware inputs or outputs exists that are occupied in duplicate.
Configuration 1 and Configuration 2 completed with one reset each.
As required:
Start page > Password Enter
then:
Main Index > Configuration > Check config IO's
Range
Function
11. No
Displays whether there are unassigned I/Os.
12. Yes
0, 1, ...
Displays the position of the first unassigned I/O. The associated
plant elements are available in the table in appendix 20.2
Diagnostic tables for check I/O.
13. No
Displays whether hardware input or outputs are occupied in dupli-
14. Yes
cate.
Displays positions of the first double occupancy. The associated
plant elements are available in the table in appendix 20.2
Diagnostic tables for check I/O.
XO1...XO28
Displays the first double occupied input or output (exception: DO).
DO1...DO24
Displays first double occupied DO.
0... [pcs]
Displays number of unused universal inputs/outputs.
0... [pcs]
Displays the number of unused digital inputs.
0... [pcs]
Displays the number of unused analog outputs.
0... [pcs]
Displays the number of unused digital outputs.
Standard application AHU