Preparation
Content of configuration
page
Line
Configuration by
Configuration 1
Configuration 2
Configuration IO's
Check Config IO's
Doubled
Not Configured
Note
Siemens
Building Technologies
Enter password for level 4:
Select Start page, enter password --->
Select Main Index page, Configuration --->
Configuration page
The configuration page includes the following lines and associated parameters:
Parameter
Explanation
Select configuration type.
Download
You can download a preconfigured plant using the Saphir Scope
tool or from a SD card.
You must reset the controller after the download.
In this mode, all objects in Saphir Scope Tool and line in HMI are
visible.
HMI Config
The plant is configured in stages using the operator unit.
Requirement: List of all I/Os. It displays the available I/O's and the
I/O position they are suppose to occupy.
You also need the sensor type for sensors.
This is the normal mode that must be selected to start the plant.
Caution: You cannot change over from HMI Config to
download while the plant is running. This would immediately
shut down all outputs and reset the controller!
NotDone
Link to Configuration 1 page and displays whether or not parame-
Done
terization of Configuration 1 was completed.
NotDone
Link to Configuration 2 page and displays whether or not parame-
Done
terization of Configuration 2 was completed.
NotDone
Link to Configuration I/Os page and displays whether or not
Done
parameterization of Configuration I/Os was completed.
To Check Config I/Os page.
Fault
Displays whether an input or output can be used multiple times.
OK.
Fault generates an alarm that locks the plant.
Fault
Displays whether a function is enabled and the required I/Os are
OK.
not assigned. Fault generates an alarm that locks the plant.
The plant cannot be starting without Configuration By=HMI config and
Configuration 1=Done, Configuration 2=Done, Configuration IO's=Done.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Configuration
153 / 244
CE1P3977en_02
Page 153
01.02.2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Oem seriesPol955Pol638 series

Table of Contents