Cooling demand
Heating demand
Note
Parameter
Parameter
Start stpt cooling
Cooling setpoint
Start stpt heating
Heating setpoint
Hysteresis
Minimum off time
Min run time
Prerequisite:
Function
Cooling demand
Heating demand
Note
Siemens
Building Technologies
The plant night start by temperature difference for cooling demand occurs when
the following conditions are met:
– Room tmp > Start stpt cooling und
– Timer Minimum off time = 0
The shutdown occurs for:
– Room tmp < Start stpt cooling - Hysteresis
The plant night start by temperature difference for heating demand occurs when
the following conditions are met:
– Room tmp > Start stpt heating und
– Timer Min off time = 0
The shutdown occurs for cooling demand occurs for:
Room tmp > Start stpt heating + Hysteresis
The function when the room temperature sensor (return air sensor) fails.
Main Index > Unit > Operating mode > Tmp start
Range
Function
-64.0....64.0 [°C]
Start temperature for cooling.
-64.0....64.0 [°C]
Cooling setpoint.
-64.0...64.0 [°C]
Start temperature for heating.
-64.0....64.0 [°C]
Heating setpoint.
0.1...64.0 [°C]
Shutdown hysteresis.
0...999 [min]
Minimum switch-off time after active heating or cooling.
0.0.....999.0 [min]
Minimum runtime after a start.
5.2.8
Boost function (boost plant start)
Boost is enabled:
Main Index > Configuration > Configuration 2 > Boost <> No
Boost ensures a comfortable room temperature when the plant is switched on nor-
mally.
The heating and or cooling start can be enabled separately:
Main Index > Configuration > Configuration 2 > Boost
The function can be implemented using a return air sensor if no room sensor is
available.
Boost for cooling demand occurs when the following conditions are met:
– Room tmp > Start stpt cooling + Hysteresis and
– Time to normal start via the time switch program < Compensation time
The shutdown occurs for:
– Room tmp < Start stpt cooling
Boost for heating demand occurs when the following conditions are met:
– Room tmp < Start stpt heating - Hysteresis and
– Time to normal start via the time switch program < Compensation time
The shutdown occurs for:
– Room tmp > Start stpt heating
The function when the room temperature sensor (return air sensor) fails.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Functions
45 / 244
CE1P3977en_02
Page 45
01.02.2010