Parameter
Humidity control
Configuration
Parameter
Hum control mode
Hum control unit
Hum stpt selection
Dehum tmp prio
Dew point control
Hum deviation alarm
Humidifier pump
Hum pump alarm
Humidifier fdbk
Note
84 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 84
BDCX.100820.01GB
Building Technologies
Range
– DX2steps
– DX3steps
– No
– Hum
– Dehum
– Hum+Dehum
Main Index > Configuration > Configuration 2
Range
– No
– Room
– Supply
– RoomCasc
– Relative
– Absolute
– CacsRelAbs
– Hum/Dehum
– +/- HalfDz
– Hum+Dz
– dehum-Dz
– No
– Yes
– No
– Yes
– No
– Room/Exh
– Supply
– Sply+RmExh
– No
– Yes
– Yes+Kick
– No
– Alarm
– Fdbk
– Both
– No
– Yes
Feedback can only be used as alarm, when Contact function = NO (Normally
Open) and the element is set to ON.
Standard application AHU
Functions
Function
gate.
– (additional) 2 step direct expansion evaporator aggre-
gate.
– (additional) 3 step direct expansion evaporator aggre-
gate.
– No humidification and dehumidification.
– Humidification only.
– Dehumidification only.
– Humidification and dehumidification.
Function
Type of humidity control.
– No humidity control.
– Room control only.
– Supply air temperature control only.
– Room / supply air temperature cascade control.
Type of humidity control.
– Relative humidity control.
– Absolute humidity control.
– Cascade control with relative room and absolute supply
air humidity control.
Predefined variants for humidity setpoints:
– Humidification and dehumidification setpoint is entered
directly.
– Base setpoint and dead zone is entered.
– Humidification setpoint and dead zone is entered.
– Dehumidification setpoint and dead zone is entered.
Dehumidification is reduced dependent on the heating
output:
– Function not enabled.
– As of 90%, heating valve position reduces dehumidifica-
tion.
Dew point monitoring.
Monitors setpoint/actual value of humidification. An alarm
is triggered for deviations over a certain period:
– No monitoring.
– Monitors room humidity only.
– Monitors supply air humidity only.
– Monitors supply air and room humidity.
– No humidifying pump.
– Humidifying pump without pump kick.
– Humidifying pump with pump kick.
– Pump without alarm or feedback.
– Pump with alarm.
– Pump with feedback.
– Pump with alarm and feedback.
– Humidifier without feedback.
– Humidifier with feedback.
CE1P3977en_02
01.02.2010