Siemens Climatix Series Basis Document page 171

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

HW IO
Pos
Air quality sensor
NUsd,Comm,X1...X28
External setpoint
NUsd,Comm,X1...X28
Terminal positions
Note
HW IO
Outs air damper DO
Extr air damper DO
Fire damperDO
Terminal positions
Siemens
Building Technologies
15.3.7 Other
The listed hardware assigned are possible Air Quality sensor and the external set-
point adjuster/slider.
Scale (bei 10 V; 0 V = 0ppm, fix)
0...3000 ppm
---
Position
Explanation
X4...X8
Terminal on basis controller.
DI1...DI5
Terminal on basis controller.
X11...X18
Terminal on extension module 1.
X21...X28
Terminal on extension module 2.
Comm
Sensor is connected via communication and therefore does not oc-
cupy a hardware input. Some sensors can also be connected via
communication (see lists in the documentation on the basics for
LON, ModBus, BacNet).
Sensors may also be enabled in parallel as well (via hardware and
communication).
The value selector must be set accordingly when enabling via com-
munication (for details page on Analog Inputs, Sec. 6.5.2.).
NUsd
No used: The hardware position is not yet selected. The plant is
locked against switching on if an enabled sensor is set to NUsd and
the following fault issued: NotConfigured (Function enabled, but
hardware not assigned).
Parameterize external setpoints in Unit > Inputs > Other.
15.3.8 Outputs: Damper
The listed hard assignments are possible for dampers.
Pos
DO1...DO24
DO1...DO24
DO1...DO24
Position
Explanation
DO1...DO6
Terminal on basis controller.
DO11...DO14
Terminal on extension module 1.
DO21...DO24
Terminal on extension module 2.
Comm
This output is connected via communication and therefore does
not occupy a hardware input. Some output signals can also be
connected via communication (see lists in the documentation on
the basics for LON, ModBus, BacNet).
Outputs may generally be enabled in parallel as well (via hardware
and communication).
NUsd
No used: The hardware position is not yet selected. The plant is
locked against switching on if an enabled sensor is set to NUsd
and the following fault issued: NotConfigured (Function enabled,
but hardware not assigned).
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Configuration
171 / 244
CE1P3977en_02
Page 171
01.02.2010