Siemens Climatix Series Basis Document page 127

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

LON module parame-
terization
Parameter
Modules
Send heart beat
Receive heart beat
Min send interval
Use default
Note
Siemens
Building Technologies
Main Index > System overview > Communication > Comm module overview >
Module[x] LON > LON module settings
Range
0...65535 [s]
0...65535 [s]
0...65535 [s]
− Passive
− Active
The controller must be reset after changes to parameterization to assume the data.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Communication
Function
Displays module type (e.g. Pol906LON).
Set interval for sending values.
Set interval for receiving values.
Set minimum interval for sending values.
Reset parameterization to default values.
127 / 244
CE1P3977en_02
Page 127
01.02.2010