Parameter
Status
Special settings
Parameter
Gain
Int action time
Min/max limit
Function during cooling
Function during heating
Example
Siemens
Building Technologies
Range
− GESP
− UL
− LL
− REG
− UDEF
7.2.2
Special settings
Range
0...1000
0....18000 [s]
-64.0...99.0 [°C] / [% rH]
Min/max limit positiv:
− Niedrigster Control output clg = Low limit + Min/max limit
− Niedrigster Control output htg = Low limit
Min/max limit negativ:
− Niedrigster Control output clg = Low limit
− Niedrigster Control output htg = Low limit - Min/max limit
Min/max limit positiv:
− Niedrigster Control output clg = High limit
− Niedrigster Control output htg = High limit - Min/max limit
Min/max limit negativ:
− Niedrigster Control output clg = High limit + Min/max limit
− Niedrigster Control output htg = High limit
High limit = 28
Low limit = 16
Min/max limit = -2
Cooling:
− Lowest control output clg = Low limit => 16.
− Lowest control output htg = Low limit - Min/max limit => 16 – 2 = 14.
Heating:
− Lowest control output htg = High limit + min/max limit => 28 – 2 = 30.
− Lowest control output htg = High limit => 28.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Detail pages: Controller
Function
Controller status:
− Controller disabled.
− Control output = High limit.
− Control output = Low limit.
− Control mode.
− Undefined.
Go to Special settings page (at access levels 4
and 2 only).
Function
− Amplification factor (KP).
Integral action time (Tn).
Adjusts high und Low limits to end position. En-
sures the difference between heating and cool-
ing output in the end position as well as needed.
113 / 244