17.12 Operating Mode - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Inputs > Digital alarms
Parameter
Function
ClgDx fdbk
Dx Cooling Feedback
Cooling Pump
Cooling Pump alarm
ClgPump fdbk
Cooling Pump Feedback
ExtraHtg Frost
Heating 2 Frost monitor
ExtraHtg Pump
Heating 2 Pump alarm
ExtraHtgPump fdbk
Heating 2 Pump Feedback
El heating 2 alarm
Extra Electrical Heater alarm
ExtraCooling DX
ExtraDx Cooling alarm
ExtraClg DX fdbk
ExtraDx Cooling Feedback
ExtraClg Pump
Cooling 2 pump alarm
ExtraClgPump fdbk
Cooling 2 pump Feedback
Auxiliaryalarm
Auxiliary alarm
Main Index > Unit > Operating mode
Parameter
Function
Actual
Actual Status from the Unit
Unit Off
Unit On in comfort Mode
Unit On in Economy Mode
Not applicable
Boost activ
Night Cooling active
UnOccupied Heating or Cooling activ
Night kick active
Fire Damper Test active
Fire Alarm, Unit in Fire Mode
Unit Stopped and locked
Fans stay on according to cool down El Heater
Unit Startup is running
Manual operation
Only if TspFunction <= Steps
Auto = TSP
Off and Stage 1...Stage 3 = override from
HMI
Manual operation
Only if TspFunction = Steps+Tmp
Auto = TSP
Off, Eco St1..3 and Comf St1..3 = override
from HMI
Time switch program Only if TspFunction <= Steps
Actual Value from TSP; Jumpline to settings
Time switch program Only if TspFunction = Steps+Tmp
Actual Value from TSP; Jumpline to settings
From BACS
Only if TspFunction <= Steps
Auto = TSP
Off and Stage 1 ..Stage 3 = override from
BMS
From BACS
Only if TspFunction = Steps+Tmp
Auto = TSP
Off, Eco St1..3 and Comf St1..3 = override
from BMS
External control
Actual Value from External Control;
Jumpline to settings
Night kick exh tmp
Start the Unit in the Night to get actual
Value for the Return Temp
Jumpline to settings
Night cooling
Free Cooling function; Jumpline to settings
Tmp start
Start of Unit in unoccupied by Temperature
difference; Jumpline to settings
Boost
Pre Start of the Unit to Heat up or cool down
with a seperate Setpoint; Jumpline to settings
Power up delay
Delay Time for Unit start after a Power up
Siemens
Building Technologies

17.12 Operating mode

17.12.1 General
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
HMI
Value range
Unit
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
OK...Fault
Value range
Unit
Off
On/Comfort
Economy.
Na
Osstp
NightClg
UnOcc
NightKick
FireDamper
Fire
Stop.
OverRun
StartUp
Auto
Off
Stage 1...Stage 3
Auto
Off
Eco St1..Eco St33
Comf St1..Comf St3
Off
Stage 1...
Stage 3
Off
Eco
Comf
Auto
Off
Stage 1...
Stage 3
Auto
Off
Eco St1..3
Comf St1..3
Auto
Off
Stage 1...
Stage 3
0...36000
--- S ---
Standard
R S Link
x
x
x
x
x
x
x
x
x
x
x
x
Standard
R S Link
X
Off
6
Off
6
Off
6
Section:
5.2.1
Off
6
Off
6
Off
6
X
X
X
X
10
4
191 / 244
CE1P3977en_02
Page 191
01.02.2010