Siemens Climatix Series Basis Document page 161

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Parameter
Range
Fan comp room
No
tmp
Yes
Fan comp air
No
quality
Yes
Fan cmp humidity
No
Yes
Fan comp outs tmp
No
Yes
Fan htg / clg
No
Htg
Clg
Htg+Clg
Tmp stpt selection
Htg+Dz
Htg/Clg
+/- HalfDz
Clg-Dz
Ext stpt function
Relative
Absolute
Room tmp mix
Average
Minimum
Maximum.
RoomSnsr1
RoomSnsr2
RoomUnit1
RoomUnit2
Room draught limit
No
Yes
Sequence fan clg
Fan-Clg
Clg-Fan
Siemens
Building Technologies
Function
Room-temperature dependent fan compensation.
Requirement: A room or return air sensor is enabled.
Air quality-dependent fan compensation. Analog input for the sensor is
enabled.
Room humidity-dependent fan compensation.
Requirement: Room humidity sensor is enabled.
Outside air-temperature dependent fan compensation.
Requirement: Outside air sensor is enabled.
The fan is further used as a heating or cooling sequence.
No sequential impact on the fan.
Only impacts fan during the heating sequence.
Only impacts fan during the cooling sequence.
Impact on fan in both sequences.
Predefined variants for temperature setpoints:
heating setpoint and dead zone are entered.
Cooling setpoint = Heating setpoint + dead zone.
Heating and cooling setpoint is entered directly.
Base setpoint and dead zone is entered.
Heating setpoint = Base setpoint – half dead zone.
Cooling setpoint = Base setpoint + half dead zone.
Cooling setpoint and dead zone is entered.
Heating setpoint = Cooling setpoint – dead zone.
Sets whether the external setpoint acts as setpoint compensation or in
absolute terms.
Value corresponds to the comfort setpoint dependent on the switch
Tmp setpoint selection.
If the switch Tmp setpoint selection is on HtgClgSpv, the value of the
setpoint compensation corresponds to the heating setpoint and the
cooling setpoint is calculated from the difference between the entered
setpoints for heating and cooling.
Setpoint compensation.
Absolute
Selection of room temperature used for control if more than one ex-
ists.
Average.
Lowest temperature.
Highest temperature.
Room sensor 1.
Room sensor 2.
Room unit 1 (not yet implemented).
Room unit 2 (not yet implemented).
Limitation to maximum/minimum supply air temperature dependent on
room temperature.
Requirements: One cascade control is enabled.
Function minimizes draughts caused by too large a difference be-
tween supply air and room temperature.
Sets sequence of fan sequence and cooling sequence.
Requirement: Fan htg / clg is enabled.
Fan sequence before cooling sequence.
Cooling sequence before fan sequence.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Configuration
161 / 244
CE1P3977en_02
Page 161
01.02.2010